What changed
The Department of Energy changed both the test (SEER2 uses higher, more realistic duct pressure, so the numbers are lower than old SEER for the same unit) and the minimums. For equipment manufactured from 1 January 2023:
| Equipment | Minimum |
|---|---|
| Split-system heat pump (all regions) | 14.3 SEER2 |
| Split-system AC, North | 13.4 SEER2 |
| Split-system AC under 45,000 Btu/h, South and Southwest | 14.3 SEER2 |
| Split-system AC 45,000 Btu/h and up, South and Southwest | 13.8 SEER2 |
The Southwest also has EER2 minimums.
Why it matters for an old unit
A pre-2023 system can stay in service and be repaired. When it is replaced, the new one must meet the current minimum for your region, and in the South and Southwest that is enforced on the installation date, not just the build date. Compare running costs using SEER2 figures for both units, not SEER for one and SEER2 for the other.